Elite Pump Controller

Wiring for a Float Switch Application

DIN8, RELAY4, and a DIN8 I/O card are required. The channel assignments for float switch sensors are:

Channel NumberOperation
Chan 11, Pump 1 AutoNormally Closed input. Puts pump in Auto mode
Chan 12, Pump 2 AutoNormally Closed input.Puts pump in Auto mode
Chan 13, Pump 1 Hand/OffTurns pump on or off manually.
Chan 14, Pump 2 Hand/OffTurns pump on or off manually.
Chan 15, Pump 1 run timeNormally Open input. Signal indicating when pump 1 is actually running, the system computes run time and number of starts.
Chan 16, Pump 2 run timeNormally Open input. Signal indicating when pump 1 is actually running, the system computes run time and number of starts.
Chan 17, Pump 1 overtempNormally Open input. Keeps pump off when overtemp condition exists.
Chan 18, Pump 2 overtempNormally Open input.Keeps pump off when overtemp condition exists.
Chan 21, Pump 1 relayControl output to turn pump on/off
Chan 22, Pump 2 relayControl output to turn pump on/off
Chan 23, SPARE relay 
Chan 24, SPARE relay 
Chan 31, Low alarm float switchNormally Open input.Initiates low level alarm call.
Chan 32, High alarm float switchNormally Open input.Initiates high level alarm call.
Chan 33, Lead/Lag selectSelects pump 1 or 2 as the lead pump when not in alternation mode.
Chan 34, Motor 1 starter or other faultPrevents pump 1 from running while in fault.
Chan 35, Motor 2 starter or other faultPrevents pump 2 from running while in fault.
Chan 36, Lead float switchStarts the lead pump.
Chan 37, Lag float switchStarts the lag pump.
Chan 38, Off float switchStops both pumps.

 

Wiring for a Level Sensor Application

DIN8, RELAY4, DIN4 or DIN8 and an AIN8 I/O card are required. The channel assignments for the level sensor are:

Channel NumberOperation
Chan 11, Pump 1 AutoNormally Closed input. Puts pump in Auto mode
Chan 12, Pump 2 AutoNormally Closed input.Puts pump in Auto mode
Chan 13, Pump 1 Hand/OffTurns pump on or off manually.
Chan 14, Pump 2 Hand/OffTurns pump on or off manually.
Chan 15, Pump 1 run timeNormally Open input. Signal indicating when pump 1 is actually running, the system computes run time and number of starts.
Chan 16, Pump 2 run timeNormally Open input. Signal indicating when pump 1 is actually running, the system computes run time and number of starts.
Chan 17, Pump 1 overtempNormally Open input. Keeps pump off when overtemp condition exists.
Chan 18, Pump 2 overtempNormally Open input.Keeps pump off when overtemp condition exists.
Chan 21, Pump 1 relayControl output to turn pump on/off
Chan 22, Pump 2 relayControl output to turn pump on/off
Chan 23, SPARE relay 
Chan 24, SPARE relay 
Chan 31, Low alarm float switchFloat backup for level sensor for pump control and alarming.
Chan 32, High alarm float switchFloat backup for level sensor for pump control and alarming.
Chan 33, Lead/Lag selectSelect pump 1 or 2 as the lead pump when not in alternate mode.
Chan 34, SPARE 
Chan 35, SPARE 
Chan 36, Motor 1 starter or other faultPrevents pump 1 from running while in fault and causes alarming.
Chan 37, Motor 2 starter or other faultPrevents pump 2 from running while in fault and causes alarming.
Chan 38, Phase Monitor FaultPrevents pumps from running while in fault and causes alarming.
Chan 41, Level sensor analog inputVoltage or current input from level sensor
Chan 42-48, spare AIN